Wiring a Circuit Breaker to On-Board WatchMon Supervisor
For WatchMon4.2 or WatchMon5.1 or earlier refer to version for 4 pin
How to connect the WatchMon4 to the Schneider Electric Circuit Breaker
When connecting to the controlled Outputs (that are using mosfet's) make sure that these loads do not have large inrush currents. Watchmon supervisor and expansion boards outputs are rated to 3A (default), they will fail when the inrush currents exceed their rating (x2 even for micro/milliseconds).
For large ( or unknown) loads make sure you use a external relay/SSR (solid state relays) that is appropriate for the rated purpose.
Note: Input should not be wired up where circuit breaker doesn't have a sensing circuit.
Set Expansion settings
Set Output to Critical Pulse OFF so that if in Critical state it will give 200ms pulse sent when Critical State turns to OFF used to trigger Circuit Breakers
If using a sensing input the input should be set to Critical contact sensor